SURE-BK Standard Orifice Plate Flow Meter

$0.00

Diameter: 50mm≤DN≤1000mm, if DN>1000mm, real flow calibration is required

Aperture Ratio β: 0.20≤β≤0.75

Pressure: PN≤16MPa

Reynolds No. Range: When 0.20≤β≤0.45, 5000≤ReD; When 0.45≤β≤0.75, 10000≤ReD

Range Ratio: 1:5, 1:10, 1:65


We will be in contact with you within two business days.

Category:

– When installing, ensure that the center of the orifice plate, the axis of the flange, the axis of the pipe, the axis of the pipe and the gasket are concentric, and the non-concentricity shall not exceed 0.002D/β

– The direction of high and low pressure of the orifice plate, the upstream and downstream pressure-taking flanges should be consistent with the flow direction of the medium, and the orientation of the pressure-taking holes can be determined according to the different media and the installation of the transmitter (refer to the SURE-BK manual).

–  Optional with upstream and downstream straight pipe sections.

– The D-D/2 pressure gauge is supplied as a complete set, and the flange connection can be directly installed.