ES22-A02-B01

$0.00

Intelligence、Communication、Visualization

Cross-Domain IIoT Protocol Gateway
DI*6 / DO(NPN)*6 / VI/VO*3 / AI/AO*3

» Support all mainstream Serial and Ethernet protocols(500+)
»
 Dual Ethernet ports w/cross-domain IP for OT/IT integration
»
 Gateway service: Consolidate OT data to IT system
»
 IDCS for OT remote management/monitoring/maintenance
»
 Optimize for upgrading old equipment w/Serial PLC
»
 Digital signage for real-time facility status monitoring
»
 Support OPC UA
»
 MQTT: Support AWS, Azure, Alibaba Cloud and Advantech WISE-PaaS


We will be in contact with you within two business days.

Category:
Model Name ES22
Working Memory (128MB) O
Backup RAM 128KB
Serial Port COM1:RS-232/422/485    COM2:RS-485(RS-232 Optional)
Ethernet 2*RJ45 (Dual IP)
USB 2.0(Host) O
USB 2.0(Client) O
RTC O
Micro SD O
A Side Optional O
Supply Voltage Isolated 12~36Vdc±10%
Operating Temperature -10° C ~ 60° C
Relative Humidity 10% ~ 90%
Shock (Operation) Half sine, 15G, 11ms duration
Vibration (Operation) Random vibration 1 Grms (5~500 Hz)
FCC / CE YES / IEC61000-6-2 & IEC61000-6-4
Software Version PM Designer v4.0.5.31 or higher version
A02 Optional Specifications
COM3 RS-232/422/485
COM4 RS-232
CAN Bus
SIO(Safety signal contactor) Yes(2DI/2DO)
GIO(I/O Port)
Wi-Fi
4G / Wi-Fi Optional
B Side Expansion Optional
Weight(g) 271.8

 

B01 Side Expansion Specifications
Model name Channel I/O type Electrical specifications
Analog input CH0 Voltage input 0.0~10.0VDC
CH1
CH2
CH3 Current input 0.0~20.0mA
CH4
CH5
Digital input CH6 Digital input NPN/PNP : DC24V /5mA
CH7
CH8
CH9
CH10
CH11
Digital output CH12 Digital output BJT(NPN) : DC24V / 0.7A
CH13
CH14
CH15
CH16
CH17
Analog output CH18 Voltage output 0.0~10.0VDC
CH19
CH20
CH21 Current output 0.0~20.0mA
CH22
CH23

 